Guide · Life Safety & Continuity
Emergency Response Planning for Facility Managers
What the regulations actually require, how to run the risk assessment, the four protective actions to decide in advance, the annexes your building needs, and how to exercise the plan so it works at two in the morning.
The plan you will actually use is short
Nobody reads a 200-page binder during a flood.
The first minutes of an emergency decide most of the outcome, and FEMA makes that point plainly: fast action and effective warning save lives and limit damage. What makes action fast is not the length of the plan. It is that the decisions were already made, the roles were already assigned, and the people who have to execute have practiced.
This guide builds an emergency response plan for a building rather than for an office. It assumes you are responsible for systems — fire protection, power, water, ventilation, access control, vertical transportation — and for coordinating with tenant employers who own their own occupants.
1. Start with what the regulations require
Federal workplace safety rules set the floor. An emergency action plan must be written, kept at the workplace, and available for employees to read; employers with ten or fewer employees may communicate it orally. At minimum it has to address six things:
- How to report a fire or other emergency.
- Evacuation procedures, including the type of evacuation and who uses which exit route.
- Procedures for anyone who stays behind to shut down or operate critical equipment before leaving.
- How everyone is accounted for once they are out.
- Procedures for employees assigned rescue or medical duties.
- The name or job title of the people who can answer questions about the plan.
Three related obligations sit alongside it. An employee alarm system must exist, be maintained, and use a distinctive signal for each purpose. Employees must be designated and trained to help others evacuate safely. And the plan must be reviewed with each covered employee when it is written, when they are hired into the job, when their responsibilities change, and whenever the plan changes. Separately, exit routes, doors, signage, and emergency lighting have to be kept usable and unobstructed at all times, and fire prevention plans carry their own requirements where they apply.
Multi-tenant buildings
The building owner is usually not the employer of the people inside. Your base-building plan has to interlock with each tenant employer’s own plan: shared alarm signals and their meaning, assembly point assignments, floor warden coverage, accountability reporting to a single point, and who has authority to order a partial evacuation. Put these in the lease exhibit or the tenant handbook, and re-confirm them whenever a tenant changes.
2. Run the risk assessment before you write procedures
A risk assessment identifies the hazards that could affect the property and works through what would actually happen in each scenario. FEMA’s guidance emphasizes looking specifically for vulnerabilities — weaknesses in construction, process systems, security, protection systems, and loss-prevention programs — because those are what turn an incident into a loss. Where the potential impact is significant, mitigation should be funded before response planning is polished.
Walk the building against this list. Every item is a real vulnerability found in real portfolios:
- Single points of failure in normal power, transfer switches, domestic water, sanitary lift stations, and vertical transportation.
- Standby power reality — what the generator actually carries, fuel on hand versus runtime needed, last load-bank test, and refueling contract.
- Fire protection impairments — valves closed for construction, out-of-service devices, hot-work controls, and whether a fire watch procedure exists in writing.
- Envelope and drainage — roof condition, drains and scuppers, sump pumps, below-grade penetrations, and where water goes when it gets in.
- Egress under stress — stair capacity, door hardware behavior on alarm, refuge areas, and evacuation plans for occupants with mobility, vision, or hearing disabilities.
- Notification coverage — dead zones for alarm audibility, mass notification reach, and after-hours contact accuracy.
- Dependencies — building automation, access control, and elevator monitoring that fail with the network rather than with the building.
Then rank what has to keep running. A business impact analysis, run with the operating leaders rather than by facilities alone, is what turns a hazard list into recovery priorities and tells you which systems justify redundancy.
3. The ten-step build
FEMA’s Ready Business program lays out a ten-step sequence for developing an emergency response plan. Paraphrased for a facilities audience, with the facility manager’s job in each step:
| # | Step | What it looks like in a building |
|---|---|---|
| 1 | Revisit your program objectives | Agree in writing what the plan is protecting: life safety first, then compliance, then property, then continuity of operations. |
| 2 | Review the hazards from your risk assessment | Carry forward only the scenarios credible for this location and this building type. |
| 3 | Assess resources for stabilizing an incident | Inventory people, systems, and equipment on site and available under contract: spill kits, water extraction, temporary power, board-up, restoration. |
| 4 | Talk to your local responders | Confirm response times, walk them through the building, share hazard locations, and pre-plan access, keys, and connections. |
| 5 | Identify the regulations that apply | Workplace safety rules, the fire code and its inspection obligations, and any state or local emergency planning requirements. |
| 6 | Develop protective actions for life safety | Evacuation, shelter, shelter-in-place, and lockdown, decided per hazard rather than improvised. |
| 7 | Write hazard-specific procedures | Short annexes, one per scenario, with names, numbers, and system actions. |
| 8 | Coordinate planning with responders | Pre-incident planning documentation so the fire department arrives already knowing your building. |
| 9 | Train people for their roles | Floor wardens, sweep teams, engineers with utility isolation duties, security, and the after-hours on-call chain. |
| 10 | Exercise the plan | Tabletops, drills, and functional exercises — then fix what they expose. |
4. Pre-decide the four protective actions
Almost every building emergency resolves into one of four protective actions. Deciding which applies to which hazard in advance — and pre-scripting the system moves that support it — is the highest-value hour you will spend on this plan.
| Action | Triggers | The facility manager’s moves |
|---|---|---|
| Evacuate | Fire, smoke, explosion, gas odor, structural concern, bomb threat | Route assignments by floor, assembly points with a bad-weather alternate, sweep and accountability teams, elevator recall, smoke control or air handler shutdown, stair pressurization, responder access and annunciator panel staffing. |
| Shelter (severe weather refuge) | Tornado warning, damaging straight-line wind, hail | Identify best-available refuge areas away from glazing and exterior walls, confirm capacity, sign and rehearse the routes, and pre-assign who sweeps upper floors and perimeter offices. |
| Shelter in place | External airborne hazard, hazardous material release nearby, heavy smoke outdoors | Pre-written sequence to shut down outside air, close dampers, and stop exhaust; identify the rooms to use; stage sealing materials; know how long the space stays habitable. |
| Lockdown | Violent intruder, external police action, security threat | Know exactly how door hardware and access control behave when locked down, how mass notification reaches every space, how responders get in fast, and how a controlled release is ordered and communicated. |
The conflict nobody plans for
Fire alarm activation often unlocks doors. Lockdown requires them locked. Severe weather sheltering moves people toward the building core while a fire alarm moves them out. Write down which action wins when two are signaled at once, and make sure security, engineering, and the alarm programming all reflect the same answer.
5. Command, roles, and the first fifteen minutes
Align your structure to the national incident management framework used by the responders who will arrive: one identified incident commander, a manageable span of control, and documented delegation of authority for nights, weekends, and vacations. The most common failure in building emergencies is not a missing procedure — it is three people each assuming someone else called the fire department.
A first-fifteen-minutes card, posted at the engineering office and the security desk:
- Confirm and classify the event. Location, type, extent, people involved.
- Protect life first. Order the protective action; do not wait for certainty.
- Call 911, then call the internal notification tree. In that order.
- Isolate what is making it worse. Power, gas, water, ventilation, fuel, conveyance.
- Account for people. Sweep teams report to one person, who reports one number.
- Control access. Stage responders, keep everyone else out, protect the scene.
- Start a written log with times. It will matter for insurance, regulators, and the after-action review.
- Notify leadership, tenants, and the insurer with facts only, on the pre-approved template.
6. The annexes your building needs
Keep each annex to a single page: trigger, immediate actions, who to call, and what to document. These are the scenarios that come up repeatedly in commercial and institutional portfolios.
| Scenario | Immediate facility actions |
|---|---|
| Fire or smoke | Evacuate the affected and adjacent zones, recall elevators, activate smoke control, staff the fire alarm panel to guide responders, isolate fuel and gas, log the alarm history. |
| Sprinkler discharge or major water leak | Locate and close the controlling valve, then treat the system as impaired: post a fire watch, notify the alarm monitoring company and the insurer, start extraction within hours to limit mold exposure, and restore protection before the building repopulates. |
| Loss of normal power | Confirm transfer to standby, verify life-safety and egress lighting, check elevator status for entrapments, protect refrigeration and critical loads, track generator fuel and runtime, and set a threshold for ordering refueling. |
| Loss of water, steam, or gas | Assess whether fire protection is affected first, then occupiability — restrooms and makeup water usually drive the decision to close. |
| Elevator entrapment | Establish voice contact immediately, dispatch the elevator contractor, never allow untrained extraction, and stay on the line until responders arrive. |
| Severe weather | Pre-storm walk of roof drains and loose exterior items, shelter order thresholds tied to official warnings, post-event structural and envelope inspection before reoccupancy. |
| Medical emergency | Call 911 first, direct responders to the exact location, stage the elevator, and know where the nearest AED is and when it was last checked. |
| Violent intruder or security threat | Lockdown per the pre-scripted sequence, mass notification, responder access and floor plans, controlled release, and immediate support resources for occupants afterward. |
| Suspicious package or substance | Do not handle or move it, isolate and restrict the area, shut down local ventilation, evacuate as directed, and let responders own the assessment. |
| Indoor air quality event | Relocate occupants out of the affected zone, isolate the air handler serving it, investigate source before adjusting anything else, and document readings and actions. |
| Network or control system outage | Know what fails with the network: building automation, access control, elevator monitoring, alarm transmission. Have manual overrides written down and practiced, and a paper fallback for access and logging. |
7. Notification and crisis communication
- One source of truth. Name the single person or role authorized to issue building-wide messages, with a named backup.
- Pre-written templates. Draft the first message for each annex now: what happened, what to do, when the next update comes. Nobody writes well under stress.
- Redundant channels. Mass notification plus SMS plus email plus physical signage at entrances. Assume one channel is down.
- Accessible messaging. Visual and audible notification, and messages readable by assistive technology.
- A contact matrix you actually maintain. Tenant emergency contacts, on-call vendors by trade, utility emergency lines, alarm monitoring, insurer, restoration contractor. Re-verify quarterly; this list is stale within months.
8. Life-safety systems only work if they were maintained
Response plans quietly assume that sprinklers flow, alarms sound, extinguishers are charged, exit lights work, and the generator starts. Those assumptions are only as good as the inspection, testing, and maintenance program behind them — the water-based fire protection, fire alarm, and portable extinguisher standards all define recurring obligations, and exit routes and alarm systems must be kept functional at all times under workplace safety rules.
Two practical consequences. First, code-driven inspection and testing belongs in the same schedule as everything else, not in a vendor portal nobody opens. Second, you need a written impairment procedure: who can take fire protection out of service, what compensating measures apply, who is notified, and how the impairment is closed out. That procedure is used far more often than the emergency plan itself. The mechanics are covered in Preventive Maintenance Planning 101.
9. Train it, then exercise it
Training is a regulatory requirement, and exercising is the final step in FEMA’s process for a reason: a plan that has never been tested is a hypothesis. A workable annual cadence:
| Activity | Frequency | Who |
|---|---|---|
| Plan orientation | At hire, at role change, and whenever the plan changes | All building staff, floor wardens, tenant contacts |
| Tabletop exercise | Quarterly, one annex per session | Engineering, security, property management, key tenants |
| Evacuation and shelter drill | Semiannual, alternating the two | Whole building |
| Functional exercise with responders | Annual | Staff plus fire department, and utility where relevant |
| After-action report | Within ten business days of every drill or real incident | Incident commander, with corrective actions and owners |
| Plan revision | Within thirty days of the after-action report | Plan owner |
Track the corrective actions like work orders, with an owner and a due date. Exercises that generate findings nobody closes are worse than no exercise, because they document a known problem you did not fix.
10. The grab-and-go packet
One binder or tablet, one duplicate off site, reviewed twice a year:
- The plan and every annex, each one page.
- Site and floor plans marking exits, refuge areas, valve and shutoff locations, panels, and hazardous material storage.
- Utility shutoff procedures with photos of the actual valves and breakers in your building.
- Current contact matrix, including after-hours numbers.
- Fire protection impairment forms and fire watch log.
- Alarm and life-safety system inventory with last test dates.
- Insurance policy numbers and the first-notice-of-loss procedure.
- Blank incident log sheets and a camera or charged phone.
- Keys, access credentials, and the elevator key cabinet location.
Continuity is the other half
Response protects people and stops the incident. Continuity gets the organization operating again. Once your response plan is exercised, build the continuity and IT recovery plans on top of the same business impact analysis rather than starting over.
Sources
Regulators, federal emergency management agencies, standards bodies, and industry associations. No software or service vendors are cited as evidence in this guide.
- OSHA, 29 CFR 1910.38, emergency action plans — written plan requirement, six minimum elements, alarm system, designated and trained evacuation assistants, and plan review triggers.
- OSHA, 29 CFR 1910.39, fire prevention plans.
- OSHA, 29 CFR 1910.37, maintenance, safeguards and operational features for exit routes.
- OSHA, 29 CFR 1910.165, employee alarm systems.
- OSHA, Evacuation Plans and Procedures eTool.
- FEMA / Ready.gov, Emergency Response Plan — source of the ten-step development process.
- FEMA / Ready.gov, Risk Assessment — hazard identification, vulnerability analysis, and mitigation priority.
- FEMA / Ready.gov, Business Impact Analysis.
- FEMA / Ready.gov, Business Continuity Planning and IT Disaster Recovery Plan.
- FEMA / Ready.gov, Crisis Communications Plans.
- FEMA / Ready.gov, Training and Testing and Ready Business toolkits.
- FEMA, National Incident Management System.
- National Fire Protection Association, NFPA 1600, continuity, emergency and crisis management.
- National Fire Protection Association, NFPA 25, NFPA 72, and NFPA 10 — inspection, testing and maintenance obligations for the systems this plan depends on.
- BOMA International, security and emergency preparedness resources.
- U.S. Environmental Protection Agency, Introduction to Indoor Air Quality — background for indoor air quality events.
Keep the plan current, not archived